Components


HEAT EXCHANGER-STEAM TO HOT WATER

COMPONENT

FUNCTION

MAINTENANCE

INLET AND OUTLET

  • Provides connections to the hot water system.
  • Check for leaks.
  • Measure temperature pick-up for efficiency.
  • CONTROL VALVE

  • Modulates steam according to system demand.
  • Check for proper operation, close off and bonnet leakage.
  • Repack, redisc, reseat and lubricate.
  • TRAP

  • Provides economic use of steam.
  • Check element, seat, float and needle valve.
  • Clean as required.
  • Repair or replace maintainable items.
  • TUBES

  • Separates steam and hot water and provides heat transfer surface from the steam to the hot water.
  • Inspect for damage or leaks.
  • Clean as required.
  • SHELL

  • Provides housing for tubes and steam.
  • Inspect for damage or leaks.
  • Clean and paint as required.