COMPONENT |
FUNCTION |
MAINTENANCE |
|
ABSORBER CONTROL CENTER |
Provides safety interlock and load control. |
Sequence test all controls.
Clean controls, calibrate and adjust safety devices.
Check for air leaks and/or electrical connections.
|
|
PURGE UNIT (Purge motor, purge pump, purge solenoid valve, purge shut off valve) |
Removes non-condensables from system. |
Lubricate motor.
Change purge unit oil.
Check drive belt and adjust tension.
|
|
REFRIGERANT PUMP
ABSORBER PUMP
CONCENTRATOR PUMP |
Circulates refrigerant in evaporator.
Circulates refrigerant in absorber.
Pumps solution to concentrator. |
Perform vibration test.
Lubricate motor and pump bearings.
Inspect gaskets and seals for leakage and deterioration.
Clean and paint as required.
Clean pump motor cooling water strainer.
|
|
SOLUTION SERVICE VALVES |
Provides access to system solution. |
Add octyl alcohol as required.
Draw solution sample and test to manufacture specification.
|
|
EVAPORATOR |
Provides for heat transfer between chilled water and refrigerant. |
Inspect and clean water side as necessary.
Inspect connection for leaks.
Repair or tighten access plate as required.
Inspect nozzles.
|
|
ABSORBER |
Allows refrigerant vapor to be drawn out of the evaporator. |
Inspect and clean water side as necessary.
Inspect connections for leaks.
Repair or tighten access plate as required.
|
|
ECONOMIZER (VALVE) |
Controls solution flow to concentrator. |
Check valve operation.
Replace motor diaphragm.
|
|
ELECTRIC CONTROL PANEL |
Provides internal control and safety for unit. |
Check safety controls.
Clean, calibrate and adjust.
Inspect starters, replace worn contacts.
Check current draw with amprobe.
Perform megger test.
|
|
STEAM SUPPLY CONDENSATE TRAP RETURN |
Provides measured steam for operation and returns condensate to boiler. |
Check steam valve operation.
Clean strainer.
Replace diaphragm as required.
Repair or replace maintainable trap items.
Inspect connection.
Clean and paint as required.
|
|
GENERATOR |
Adds heat in the form of steam or hot water to boil off the refrigerant from the absorbent to reconcentrate the solution. |
Inspect and clean water side as necessary.
Inspect connections for leaks.
Repair or tighten access plate as required.
|
|
CONDENSER |
Condenser water vapor produced in the generator by circulating water through the unit. |
Inspect and clean water side as necessary.
Inspect connections for leaks.
Repair or tighten access plate as required.
|