Components


ROOFTOP HVAC

COMPONENT

FUNCTION

MAINTENANCE

ELECTRICAL DISCONNECT

  • Provides primary electrical power safety shutoff.
  • Inspect contacts and loose connections.
  • Check for proper operation.
  • CONDENSER FAN MOTOR

  • Provides energy source for fan.
  • Perform vibration test.
  • Lubricate bearings.
  • Examine motor mount resiliency.
  • Check motor insulation resistance.
  • MOTOR STARTER

  • Controls on/off operation of motor.
  • Inspect starter coils and contacts.
  • Tighten all electrical connections.
  • Check operating current, voltage and heater size.
  • CONDENSER FAN

  • Circulates air through condenser coil
  • Check fan wheel and clean dirt accumulation.
  • Lubricate bearings and check for end play, excessive bearing temp and wear.
  • Check condition of drive couplings and belts.
  • Adjust as required.
  • Check for corrosion and wear.
  • CONDENSER COIL

  • Converts refrigerant from high temp/high pressure gas to low temp/high pressure liquid.
  • Provides efficient heat transfer.
  • Clean finned surfaces.
  • Check for damage or leaks.
  • Straighten bent fins.
  • REFRIGERATION CONTROL PANEL

  • Provides safety interlocks and controls for compressor operation.
  • Sequence test all controls.
  • Calibrate and clean controllers and safety controls.
  • Check setpoint of controls and limits.
  • REFRIGERATION COMPRESSOR

  • Prepares refrigerant to be condensed and reused at the evaporator.
  • Check crankcase heater operation.
  • Check refrigerant charge.
  • Check for refrigerant and oil leaks.
  • Check oil level and condition.
  • Perform acid test.
  • Observe bearing and operating surface temperatures.
  • Measure vibration.
  • ZONE CONTROL ACTUATORS

  • Operates zone dampers on demand from space control.
  • Inspect, clean and calibrate.
  • Adjust linkage as necessary.
  • COOLING COIL

  • Provides cooling for space being served.
  • Inspect and clean as required.
  • Check condition of finned surfaces and straighten if bent.
  • Check for corrosion and leaks.
  • FILTER SECTION

  • Provides source of clean air for unit.
  • Replace media as required.
  • FRESH AIR DAMPER

  • Provides source of outside air.
  • Check for unrestricted and proper operation and close-off.
  • Lubricate bearings as required.
  • RETURN AIR DAMPER

  • Provides source of recirculated air from the building.
  • Check for unrestricted and proper operation and close-off.
  • Lubricate bearings as required.
  • EXHAUST AIR DAMPER

  • Provides outlet for exhausted air from building.
  • Check for unrestricted and proper operation and close-off.
  • Lubricate bearings as required.
  • RETURN AIR FAN

  • Circulates return air from building.
  • Lubricate bearings and check for end play, excessive bearing temp. and wear.
  • Check blower and clean dirt accumulation.
  • Check condition of drive couplings and belts.
  • SUPPLY FAN

  • Circulates conditioned air to areas being served by unit.
  • Check for alignment, balance and security to shaft.
  • Check rotation.
  • RETURN AIR FAN MOTOR

  • Provides energy source for return air fan
  • Perform vibration test.
  • Lubricate bearings.
  • Check motor isulation resistance.
  • Examine motor mount resiliency.
  • SUPPLY MOTOR

  • Provides energy source for main fan.
  • Same as above.
  • MOTOR STARTER

  • Controls on/off operation of motor.
  • Inspect starter coils and contacts.
  • Tighten all electrical connections.
  • Check operating current, voltage and heater size.
  • BURNER SECTION

  • Provides combustion controls, fuel regulating equipment and safety controls for heating section.
  • Perform combustion and draft tests.
  • Inspect and clean nozzles.
  • Inspect, clean and lube burner fan (gun type burners)
  • Test safety controls.
  • HEATING SECTION

  • Provides heat source for areas being served.
  • Inspect and clean as required.
  • Check for leaks in echanger.
  • ZONE DAMPERS

  • Provides source for conditioned air being delivered to areas served by unit.
  •