COMPONENT |
FUNCTION |
MAINTENANCE |
|
ELECTRICAL DISCONNECT |
Provides primary electrical power safety shutoff. |
Inspect contacts and loose connections.
Check for proper operation.
|
|
CONDENSER FAN MOTOR |
Provides energy source for fan. |
Perform vibration test.
Lubricate bearings.
Examine motor mount resiliency.
Check motor insulation resistance.
|
|
MOTOR STARTER |
Controls on/off operation of motor. |
Inspect starter coils and contacts.
Tighten all electrical connections.
Check operating current, voltage and heater size.
|
|
CONDENSER FAN |
Circulates air through condenser coil |
Check fan wheel and clean dirt accumulation.
Lubricate bearings and check for end play, excessive bearing temp and wear.
Check condition of drive couplings and belts.
Adjust as required.
Check for corrosion and wear.
|
|
CONDENSER COIL |
Converts refrigerant from high temp/high pressure gas to low temp/high pressure liquid.
Provides efficient heat transfer. |
Clean finned surfaces.
Check for damage or leaks.
Straighten bent fins.
|
|
REFRIGERATION CONTROL PANEL |
Provides safety interlocks and controls for compressor operation. |
Sequence test all controls.
Calibrate and clean controllers and safety controls.
Check setpoint of controls and limits.
|
|
REFRIGERATION COMPRESSOR |
Prepares refrigerant to be condensed and reused at the evaporator. |
Check crankcase heater operation.
Check refrigerant charge.
Check for refrigerant and oil leaks.
Check oil level and condition.
Perform acid test.
Observe bearing and operating surface temperatures.
Measure vibration.
|
|
ZONE CONTROL ACTUATORS |
Operates zone dampers on demand from space control. |
Inspect, clean and calibrate.
Adjust linkage as necessary.
|
|
COOLING COIL |
Provides cooling for space being served. |
Inspect and clean as required.
Check condition of finned surfaces and straighten if bent.
Check for corrosion and leaks.
|
|
FILTER SECTION |
Provides source of clean air for unit. |
Replace media as required.
|
|
FRESH AIR DAMPER |
Provides source of outside air. |
Check for unrestricted and proper operation and close-off.
Lubricate bearings as required.
|
|
RETURN AIR DAMPER |
Provides source of recirculated air from the building. |
Check for unrestricted and proper operation and close-off.
Lubricate bearings as required.
|
|
EXHAUST AIR DAMPER |
Provides outlet for exhausted air from building. |
Check for unrestricted and proper operation and close-off.
Lubricate bearings as required.
|
|
RETURN AIR FAN |
Circulates return air from building. |
Lubricate bearings and check for end play, excessive bearing temp. and wear.
Check blower and clean dirt accumulation.
Check condition of drive couplings and belts.
|
|
SUPPLY FAN |
Circulates conditioned air to areas being served by unit. |
Check for alignment, balance and security to shaft.
Check rotation.
|
|
RETURN AIR FAN MOTOR |
Provides energy source for return air fan |
Perform vibration test.
Lubricate bearings.
Check motor isulation resistance.
Examine motor mount resiliency.
|
|
SUPPLY MOTOR |
Provides energy source for main fan. |
Same as above.
|
|
MOTOR STARTER |
Controls on/off operation of motor. |
Inspect starter coils and contacts.
Tighten all electrical connections.
Check operating current, voltage and heater size.
|
|
BURNER SECTION |
Provides combustion controls, fuel regulating equipment and safety controls for heating section. |
Perform combustion and draft tests.
Inspect and clean nozzles.
Inspect, clean and lube burner fan (gun type burners)
Test safety controls.
|
|
HEATING SECTION |
Provides heat source for areas being served. |
Inspect and clean as required.
Check for leaks in echanger.
|
|
ZONE DAMPERS |
Provides source for conditioned air being delivered to areas served by unit. |
|