COMPONENT |
FUNCTION |
MAINTENANCE |
|
STRAINER |
Removes particles from supply steam. |
Pull strainer and clean.
Check for leaks.
Check for corrosion.
|
|
DISTRIBUTION MANIFOLD |
Distribute steam to space. |
Check for proper stem flow around manifold.
Check security to duct.
Check and clean manifold slots.
|
|
CONTROL VALVE |
Modulates humidity to system according to space demands. |
Check for proper operation, close off and bonnet leakage.
Repack, redisc, reseat and lubricate.
|
|
TRAP |
Provides economic use of steam. |
Check element, seat, float and needle valve.
Clean as required.
Repair or replace maintainable items.
|